More Views

new - new product flame retardant and non corrosive (FRNC) - Comply with DIN VDE and ICE standards. Flame retardant and halogen-free cables with combustion gas that does not form aggressive acids in combination with water. Application: fi xed installations (less flexible than e.g. PVC). EN50200 - Europäisches Prüfverfahren für die Funktionsfähigkeit von Kabeln bis 20 Millimeter Durchmesser im Brandfall.

SCFX.. speaker cable - FR (fire resistant)

  • fine stranded conductors
  • fire resistance PH120 acc. to EN 50200
SPEAKER CABLE - FR, 2 x 1.0 mm², Fire Resistant

SKU: SCFX2010

cond. cross section1.0 mm2
conductor resistance≤ 19.5 Ω/km
no. of cores2
outer Ø7.0 mm
colourred
weight0,065 kg
length1 m
stock:
on request
€3.62 / m
Incl. 19% Tax, excl. Shipping Cost
incl. German VAT plus postage
SPEAKER CABLE - FR, 2 x 1.5 mm², Fire Resistant

SKU: SCFX2015

cond. cross section1.5 mm2
conductor resistance≤ 13.3 Ω/km
no. of cores2
outer Ø7.7 mm
colourred
weight0.08 kg
length1 m
stock:
on request
€4.40 / m
Incl. 19% Tax, excl. Shipping Cost
incl. German VAT plus postage
SPEAKER CABLE - FR, 2 x 2.5 mm², Fire Resistant

SKU: SCFX2025

cond. cross section2.5 mm2
conductor resistance≤ 7.98 Ω/km
no. of cores2
outer Ø8.8 mm
colourred
weight0,115 kg
length1 m
stock:
on request
€6.74 / m
Incl. 19% Tax, excl. Shipping Cost
incl. German VAT plus postage

construction

conductorstranded bare copper, fine wired acc. to IEC 60228, class 5
core insulationsilicone rubber, red & black
core arrangement2 cores twisted to a pair
outer jacketFRNC

mechanics

min. bending radius10x outer diameter
working temperature-30°C / +70°C

electric

test voltage2000 V
operating voltage100 V

fire performance

flame retardancyIEC 60332-1-2 and IEC 60332-3-25 (category D)
halogen-freeIEC 60754-1
non corrosiveIEC 60754-2
low smoke emissionIEC 61034-2
fire resistantEN 50200 (PH120)

Details

The SCFX.. cable is a halogen-free low-smoke speaker cable for connecting 100 V line -PA speaker cables with stricter safety requirements, such as those in sports stadia, airports and other event locations or venues where circuit integrity class PH120 is required. Emergency announcement system must continue to function for 120 minutes even in case of fire. Classic safety speaker cables with high conductor cross-section generally have solid conductors which may break under continuous vibrations at terminal connectors. The use of flexible Class 5 inner conductors acc. to EN 60228 standard prevents this danger. Many times they are used in Fire-detecting sytems, too.

Technical Data

construction

conductorstranded bare copper, fine wired acc. to IEC 60228, class 5
core insulationsilicone rubber, red & black
core arrangement2 cores twisted to a pair
outer jacketFRNC

mechanics

min. bending radius10x outer diameter
working temperature-30°C / +70°C

electric

test voltage2000 V
operating voltage100 V

fire performance

flame retardancyIEC 60332-1-2 and IEC 60332-3-25 (category D)
halogen-freeIEC 60754-1
non corrosiveIEC 60754-2
low smoke emissionIEC 61034-2
fire resistantEN 50200 (PH120)

Product Detail

Details

The SCFX.. cable is a halogen-free low-smoke speaker cable for connecting 100 V line -PA speaker cables with stricter safety requirements, such as those in sports stadia, airports and other event locations or venues where circuit integrity class PH120 is required. Emergency announcement system must continue to function for 120 minutes even in case of fire. Classic safety speaker cables with high conductor cross-section generally have solid conductors which may break under continuous vibrations at terminal connectors. The use of flexible Class 5 inner conductors acc. to EN 60228 standard prevents this danger. Many times they are used in Fire-detecting sytems, too.